Sign In | Join Free | My chinacsw.com |
|
Brand Name : Fanke High-voltage
Model Number : Z-VI series
Certification : ISO9001
Place of Origin : China
MOQ : One unit
Price : Negotiable
Payment Terms : T/T
Supply Ability : 10units/week
Delivery Time : 20-25 work days
Packaging Details : Export standard wooden case with fumigation free
Application : DC Hipot Tester and leakage current measurement
Test object : Electric Arresters , Insulators , Power Cable
Test Range : made by order
Duty Cycle : 30mins for one time
Current Accuracy : 1.0% of the reading ± 2digit
Voltage Accu : 1.0% of the reading ± 0.2KV
Portable DC High Voltage Generator , DC High Voltage Test Kit , DC Hipot And Leakage Current Tester
I. Product Description
Z-VI Series DC hipot tester is used for DC high voltage withstand test and leakage current measurement for zinc oxide arrester, magnetic blowing arrester, power cables, generators, transformers, switches and other equipment. It is suitable for electric power branch, power department of factories, scientific research units, railway, chemical industry, and power plants.
II. Feature
III. Technical data
Specification |
60/2 | 100/2 | 100/10 | 160/2 | 180/2 | 200/2 | 300/3 |
100/200 |
200/300 |
Others |
Voltage output (kV) | 60 | 100 | 100 | 160 | 180 | 200 | 300 | 100/200 | 200/300 |
600~800 |
Current output |
2 | 2 | 10 | 2 | 2 | 2 | 3 | 3/2 | 3/2 | |
Power output |
120 | 200 | 1000 | 320 | 360 | 400 | 900 | 400 | 600 | |
Charging current |
3.0 | 3.0 | 12.0 | 3.0 | 3.0 | 3.0 | 4.5 | 4.5/3.0 | 4.5/3.0 | |
Chassis weight |
4.3 | 4.3 | 5.3 | 4.3 | 4.3 | 4.4 | 5.5 | 4.5 | 8.1 | |
Dimension of |
Φ80 |
Φ80 |
Φ80 |
Φ80 |
Φ110 |
Φ110 |
Φ160 |
Φ110 |
Φ110 |
|
Weight of voltage multiplier tube |
6.3 | 6.8 | 7.5 | 7.2 | 7.2 | 7.2 | 7.6 | 7.5 | 12.6 | |
Polarity | Negative voltage polarity, zero voltage start, continuously adjustable | |||||||||
Working power | AC 220V ±10%; 50 Hz | |||||||||
Voltage accuracy | 1.0% ±1d, Max. resolution 0.1% kV | |||||||||
Current accuracy | 1.0% ±1d, Max. resolution 0.1% uA | |||||||||
Over-voltage error | ≤1.0% | |||||||||
0.75 |
≤0.5% | |||||||||
Ripple coefficient | ≤1.0% | |||||||||
Voltage stability | ≤0.5%, if line-voltage variation is ±10%; Random fluctuation | |||||||||
Manner of working | Intermittent service, for 30 min at rated load; for 10 min at 1.1 times of rated voltage | |||||||||
Ambient temperature | -15℃~50℃ | |||||||||
Relative humidity | If 25℃,less than 90%(non-condensing) | |||||||||
Altitude | Below 2000m |
IV. Supply List:
1, Control cabinet 1 set
2, High-voltage multi-voltage tube 1 piece(or 2 pieces)
3, Power line 1 piece
4, High-frequency output cable 1 piece
5, Fuse 10A 3 pieces
6, Instruction manual 1 copy
7, Certificate of quality 1 copy
8, Factory report 1 copy
9, Telescopic discharging rod 1 piece
10, Ground wire for discharging rod 1 piece
11, Current-limiting resistance 1 piece
12, Microampere meter 1 piece
13, Shielding wire and clamps 1 set
![]() |
Lightweight DC Hipot Test Equipment Leakage Current Tester Easy To Operate Images |